Modbus CRC Calculator
Build, inspect and diagnose frames locally in your browser. TCP tools do not connect to TCP devices.
CRC-16/MODBUS
CRC starts at 0xFFFF, polynomial 0xA001. The low byte is sent first. Modbus TCP has no RTU CRC.
Results
Run an operation to inspect the result.
Quick reference
Addresses are protocol offsets (0–65535), not 40001 reference numbers. FC01/02 read up to 2000 bits, FC03/04 up to 125 registers, FC0F writes up to 1968 coils, and FC10 writes up to 123 registers. RTU address 0 is a write broadcast and has no response.
A valid exception response reports a device-side rejection; it is not a successful read/write. Read responses do not include the starting address; compare with the request to determine register addresses.