Modbus TCP Frame Tools

Build, inspect and diagnose frames locally in your browser. TCP tools do not connect to TCP devices.

Frame builder

Frame parser

Offsets are zero-based. HEX input accepts spaces, commas, colons, hyphens and 0x prefixes. No data is sent to a device.

Results

Run an operation to inspect the result.

Quick reference

Addresses are protocol offsets (0–65535), not 40001 reference numbers. FC01/02 read up to 2000 bits, FC03/04 up to 125 registers, FC0F writes up to 1968 coils, and FC10 writes up to 123 registers. RTU address 0 is a write broadcast and has no response.

A valid exception response reports a device-side rejection; it is not a successful read/write. Read responses do not include the starting address; compare with the request to determine register addresses.