Modbus RTU and TCP Testing Tools

Build, parse and diagnose Modbus RTU/TCP frames, calculate CRC, decode register values, convert addresses and communicate with an RTU device through Web Serial. Frame and register data are processed locally in the browser.

Quick comparison

TaskRecommended toolInput / connectionOutput
Find a malformed frameFrame DiagnosticsRTU/TCP request and optional responseFields, errors and request/response comparison
Create a test frameRTU / TCPFunction, address, quantity and valuesComplete HEX request or response
Interpret register valuesRegister DecoderRegisters, type, order and scaleDecoded engineering values and CSV
Communicate with hardwareRTU Serial ClientUSB / RS-485 + Web SerialPolling data, logs and charts

How to choose

You already have captured HEX

Start with Frame Diagnostics, then move the payload to Register Decoder when the frame itself is valid.

You need a request to send

Choose RTU or TCP based on transport. Confirm whether the manual uses protocol offsets or 4xxxx references.

You need to test a real device

Use RTU Serial with a supported desktop browser and USB/RS-485 adapter. The other frame tools do not open TCP or serial connections.

Frequently asked questions

Is Modbus address 40001 sent on the wire?

Usually no. 40001 is a documentation reference for holding-register ordinal 1; the protocol address sent in the PDU is normally zero. Always confirm the device manual convention.

Do Modbus TCP frames use CRC?

No. Modbus TCP uses an MBAP header and relies on TCP integrity checks. CRC-16/MODBUS belongs to Modbus RTU serial frames.